Veeder-Root
(originally listed as Marley Pump Co.)

Red Jacket Electronics RE400-179-5 to RE400-199-5 Combination High Level/Low Level Sensor,
RE400-042-5 Hydrostatic Sensor,
Red Jacket PPM 4000 with Optical Liquid Discrimination Sensor

INTERSTITIAL DETECTOR (LIQUID-PHASE) 

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

float switch (RE400-179-5 to RE400-199-5 Combination High Level/Low level sensor, RE400-042-5 Hydrostatic Sensor), optical sensor (Red Jacket PPM 4000 with Optical Liquid Discrimination Sensor)

Test Results:
*California requires annual certification of all leak detection equipment. The certification of discriminating sensors should include functional testing of both water and product detection capabilities.

Model PPM 4000 with Optical Liquid Discrimination Sensor: This sensor can only respond to liquid directly in contact with the detection element, and is unable to detect a product release floating on an existing pool of water whose height exceeds the level of the detection element.

RE400-179-5 to RE400-199-5 Combination High Level/Low

 

unleaded gasoline

 

diesel*

 

water

Level Sensor

high

low

high

low

high

low

Detection time (sec)

<1

<1

<1

<1

<1

<1

Fall time (sec)

<1

<1

<1

<1

<1

<1

Lower detection limit (cm)

N/D**

3.80

N/D

4.26

N/D

3.53

RE400-042-5 Hydrostatic Sensor

 

 

 

 

 

 

Detection time (sec)

<1

<1

<1

<1

<1

<1

Fall time (sec)

<1

<1

<1

<1

<1

<1

Lower detection limit (cm)

30.42

4.93

30.22

4.61

29.93

4.19

Red Jacket PPM 4000 with Optical Liquid Discrimination Sensor

unleaded gasoline

synthetic fuel

  

diesel

  heating oil #2

 

 

water

Response time (min)     

2.19

2.20

1.93

2.23

2.81

Recovery time (min)      

< 1

< 1

< 1

< 1

< 1

Product activation height (cm)

1.08

1.10

1.03

1.07

1.20

Lower detection limit (cm)

0.30

N/D

N/D

N/D

N/D

*Evaluations determined these sensors' responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.

**See glossary

Specificity:
Evaluator claims RE400-179-5 to RE400-199-5 Combination High Level/Low Level Sensor and RE400-042-5 Hydrostatic Sensor will respond to any liquid once threshold has been exceeded.

Comments:
RE400-179-5 to RE400-199-5 Combination High Level/Low Level Sensor model numbers and high level detection limit vary with length of sensor.
PPM 4000 with Optical Liquid Discrimination Sensor evaluation lists all PPM, RLM, and ST models, including the Multiplexer Unit.  However, evaluation procedures were performed using model PPM 4000.
Sensors are reusable.

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT 06070-2003

Dates of Evaluation:  06/01/95,  04/28/92

Tel: (860) 651-2700

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.