Issue Date: November 22, 1995
Revision Date: December 6, 2002
Agar Corp.
LEAKWISE Groundwater Monitor
ID-220 Series Hydrocarbon on Water Detector System
Out-of-Tank Product Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Radio frequency (RF) attenuation |
Test Results
Unleaded Gasoline | Synthetic Gasoline | |
---|---|---|
Detection time (sec) | <1 | <1 |
Fall time (sec) | <1 | <1 |
Lower detection limits (cm) | ||
"Standard" setting | 0.16 | 0.32 |
"Sensitive" setting | 0.03 | 0.03 |
Specificity Results
Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s), water.
Manufacturer's specifications
Operating range:
Resolution | 0.5 mm of hydrocarbon on water or brine |
---|---|
Variation | Groundwater fluctuation of +/- 1 meter standard (larger variations optional) |
Oil thickness | 0.3 - 25 mm optional (higher ranges available) |
Temperature | 0 - 70 degrees C (higher available) |
Comments
Sensors are reusable.
Color coded signal lights indicate the presence of air, water, and hydrocarbon liquid when activated (yellow, green, and red, respectively).
- Agar Corp.
5150 Tacoma Drive
Houston, TX 77041
Tel: (832) 476-5100 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 11/15/91
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.