Issue Date: December 5, 2002

Engineering Design Group

EDG XLD 2000 Plus (Revision 1.02) Leak Detection System
(MTS DDA Magnetostrictive Probe)

Bulk Underground Storage Tank Leak Detection Method (50,000 Gallons Or Greater)

Certification Leak rate is proportional to product surface area (PSA).
For tanks with PSA of 12,074 ft2, leak rate is 1.92 gph with PD = 95% and PFA = 5%.
For other tank sizes, leak rate equals [(PSA in ft2 ÷ 12,074 ft2) x 1.92 gph].
Example: For a tank with PSA = 1,260 ft2; leak rate = [(1,260 ft2 ÷ 12,074 ft2) x 1.92 gph] = 0.2 gph.
Leak rate may not be scaled below 0.2 gph.
Leak Threshold Leak threshold is proportional to product surface area (PSA).
For tanks with PSA of 12,074 ft2, leak threshold is 0.96 gph
For other tank sizes, leak threshold equals [(PSA in ft2 ÷ 12,074 ft2) x 0.96 gph].
Example: For a tank with PSA = 1,260 ft2; leak threshold = [(1,260 ft2 ÷ 12,074 ft2) x 0.96 gph] = 0.1 gph.
A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds the calculated leak threshold.
Applicability Gasoline, diesel, aviation fuel, fuel oil #4.
Other liquids may be tested after consultation with the manufacturer.
Tank Capacity Use limited to single, field-constructed, vertical-walled tanks having a capacity of 50,000 to 2,100,000 gallons Minimum product surface area (PSA) is 1260 ft2.
Maximum product surface area (PSA) is 12,076 ft2.
Performance not sensitive to product level.
Waiting Time Minimum of 30 hours, 18 minutes after delivery or transfer.
Test Period Minimum of 40 hours, 12 minutes.
There must be no delivery, transfer, or dispensing during test.
Temperature Average for product is determined by five resistance temperature detectors (RTDs)
Water Sensor Must be used to detect water ingress.
Minimum detectable water level in the tank is 2.655 inches.
For tanks with a PSA of 12,076 ft2 and containing 2.665 inches of water, system takes 52.7 hours to detect a 0.20 gph water ingress rate.
Calibration System must be checked and, if necessary, calibrated in accordance with manufacturer's instructions.
Comments Tests only portion of tank containing product.
As product level is lowered, leak rate in a leaking tank decreases (due to lower head pressure).
Consistent testing at low levels could allow a leak to remain undetected. Evaluated in nominal 2,100,000 gallon tank with PSA of 12,076 ft2 (124 feet in diameter).
If product temperature change exceeds 1.8 degrees F during test, test will abort.
  • Engineering Design Group, Inc.
    800 Meridian Tower
    5100 E. Skelly Drive
    Tulsa, OK 74135
    Tel: (918) 628- 7100
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 11/16/01

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.