Issue Date: September 11, 1998
HT Technologies, Inc.
Vakumatik Models V 60, V 70 Ex
Continuous Interstitial Tank System Monitoring Method (Pressure/Vacuum)
Certification | Leak rate of 0.1 gph with PD =100% and PFA =0%. |
---|---|
Leak Threshold | System alarms when liquid enters interstitial space and vacuum decreases (pressure increases) above 34 millibars. |
Applicability | Gasoline, diesel. Other liquids may be tested, which are compatible with flexible liner, after consultation with the manufacturer. |
Tank Capacity | Maximum of 20,000 gallons based on interstitial volume resulting when flexible liner is properly fitted and held in position against rigid tank wall. No minimum product level during test. |
Waiting Time | None between delivery and testing. |
Test Period | Minimum of 120 hours. |
Comments | System tests the interstitial space between a properly fitted and installed flexible liner inside a rigid tank, or between the rigid walls of a double-walled tank. State Waterboard staff are currently evaluating the applicability of this method in satisfying the performance standards for continuous vacuum/pressure monitoring systems required by Assembly Bill 2481 (Chapter 6.7, Health and Safety Code, section 25290.1). Listings will be updated once a determination has been made. |
- HT Technologies
4360 Brownsboro Rd.
Louisville, KY 40207
Tel: (888) 287-9595 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Dates of Evaluation: 08/17/97, 01/28/98
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.