Issue Date: November 22, 1995
Revision Date: August 23, 1999
Mine Safety Appliances
Tankgard P/N 481532,Tankgard VIII P/N 488803
Out-of-Tank Product Detector (Vapor-Phase)
Detector
Output Type | Quantitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Metal oxide semiconductor |
Test Results
Benzene | 2-methylbutane | |
---|---|---|
Detection time (sec) | 5 | 16 |
Fall time (min:sec) | 04:12 | 04:42 |
Lower detection limit (ppm) | 12.5 | 12.5 |
Specificity Results (in addition to above)
Activated (100%): n-butane, n-hexane, 2-methylpentane, toluene, isobutane.
Manufacturer's specifications
Maximum Wire Distance | 500 ft using 18 AWG |
---|---|
Response Time | 30 seconds |
Recovery Time | 1 minute maximum |
Sensor Life | 2 year warranty |
- Mine Safety Appliances
P. O. Box 427
Pittsburgh, PA 15230
Tel: 800) 672-4678 - Evaluator: Carnegie Mellon Research Institute
Tel: (412) 268-3495
Date of Evaluation: 03/26/91, 03/28/91
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.