Issue Date: November 22, 1995
Revision Date: August 23, 1999

Mine Safety Appliances

Tankgard P/N 481532,Tankgard VIII P/N 488803

Out-of-Tank Product Detector (Vapor-Phase)

Detector

Output Type Quantitative
Sampling Frequency Continuous
Operating Principle Metal oxide semiconductor

Test Results

  Benzene 2-methylbutane
Detection time (sec) 5 16
Fall time (min:sec) 04:12 04:42
Lower detection limit (ppm) 12.5 12.5

Specificity Results (in addition to above)

Activated (100%): n-butane, n-hexane, 2-methylpentane, toluene, isobutane.

Manufacturer's specifications

Maximum Wire Distance 500 ft using 18 AWG
Response Time 30 seconds
Recovery Time 1 minute maximum
Sensor Life 2 year warranty
  • Mine Safety Appliances
    P. O. Box 427
    Pittsburgh, PA 15230
    Tel: 800) 672-4678
  • Evaluator: Carnegie Mellon Research Institute
    Tel: (412) 268-3495
    Date of Evaluation: 03/26/91, 03/28/91

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.