Issue Date: November 22, 1995
Revision Date: April 14, 2003

OMNTEC Mfg., Inc.

Controller Models Series LPD, LU, OEL8000 with Sensors L-LL-R-1, LS-ASC, PDS-ASC, PDWS-1, PDWF-1

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Refractive index of liquids (all), electrical conductivity (PDS-ASC, PDWS-1, and PDWF-1)

Test Results

  Unleaded Gasoline Diesel Water
L-LL-R-1 (low level)
Detection time (sec) <1 <1 <1
Fall time (sec) <1 <1 <1
Lower detection limit (cm) 6.63 6.53 6.45
L-LL-R-1 (high level)
Detection time (sec) <1 <1 <1
Fall time (sec) <1 <1 <1
Lower detection limit (cm) 21.7 21.8 21.7
LS-ASC , PDS-ASC
Detection time (sec) <1 <1 <1
Fall time (sec) <1 <1 <1
Lower detection limit (cm) 2.24 2.11 1.42
PDWS-1
Detection time (sec) <1 <1 <1
Fall time (sec) <1 <1 <1
Lower detection limit (cm) 1.93 1.85 1.63
PDWF-1
Detection time (sec) <1 <1 <1
Fall time (sec) <1 <1 <1
Lower detection limit (cm) 1.60 1.67 1.02

Specificity Results (in addition to above)

Activated: synthetic gasoline, n-hexane, jet-A fuel, toluene, xylene(s).
LS and PD series responds to any liquid with an index of refraction different than air.
PD series responds to any conducting liquid.

Comments

Detectors are listed as interstitial due to intended use.
Sensors are reusable.

  • OMNTEC Mfg., Inc.
    1993 Pond Rd.
    Ronkonkoma, NY 11779
    Tel: (631) 981-2001
    Email: omntec@omntec.com
    Website: www.omntec.com
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Dates of Evaluation: 06/12/93
    (Revised 11/20/98)

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.