Issue Date: November 22, 1995
Revision Date: October 18, 2002

OPW Fuel Management Systems

(originally listed as Petro Vend, Inc.)

SiteSentinel Controller with Hydrocarbon Sensitive Polymer Cables Part #30-3206, #30-3207-nn, #30-3210-nn, #30-3219-12

Out-of-Tank Product Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Product permeable

Test Results

  Unleaded Gasoline Diesel
Part #30-3206, #30-3207-nn***, #30-3210-nn***, #30-3219-12
Detection time (sec) 13.602 24.104
Fall time (min) * **

*Sensor must be cleaned and dried when exposed to hydrocarbons.

**Sensor must be replaced or threshold needs to be reset when exposed to diesel.

*** "nn" denotes a variable length in feet.

Specificity Results

Evaluator indicates that sensors respond only to hydrocarbons.

Comments

Evaluator indicates that since each of the sensors use the same polymer material, the results can be applied to any sensor with this material.

  • OPW Fuel Management Systems
    6900 Santa Fe Dr.
    Hodgkins, IL 60525
    Tel: (708) 485-4200
    URL: www.opwglobal.com/opw-fms
  • Evaluator: Underwriters Laboratories, Inc.
    Tel: (847) 272-8800
    Date of Evaluation: 12/10/92
    Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Dates of Evaluation: 8/3/00

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.