Issue Date: November 22, 1995
Revision Date: October 18, 2002

OPW Fuel Management Systems

(originally listed as Petro Vend, Inc.)

Petrosentry TLD III, SiteSentinel Smart Module and Vapor Sensor

Out-of-Tank Product Detector (Vapor-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Metal oxide semiconductor

Test Results

Petrosentry TLD III

  Benzene 2-methylbutane
Detection time (sec) 5 16
Fall time (min:sec) 4:12 0:42
Lower detection limit (ppm) 12.5 12.5

SiteSentinel Smart Module and Vapor Sensor

  Unleaded Gasoline Synthetic Gasoline JP-4 Jet Fuel
Detection time (sec) 5 7 10
Fall time (min:sec) 6:30 3:35 4:26
Lower detection limit (ppm) 10 10 10

Specificity Results (in addition to above for Petrosentry TLD III)

Activated: n-hexane, toluene, n-butane, isobutane, 2-methylpentane.

Specificity Results (in addition to above for SiteSentinal Smart Module and Vapor Sensor)

Activated: n-hexane, toluene, xylene(s).

Manufacturer's specifications

Petrosentry TLD III maximum wire distance: 500 ft using 18 AWG

  • OPW Fuel Management Systems
    6900 Santa Fe Dr.
    Hodgkins, IL 60525
    Tel: (708) 485-4200
    URL: www.opwglobal.com/opw-fms
  • Evaluator: Carnegie Mellon Research Institute
    Tel: (412) 268-3495
    Date of Evaluation: 03/26/91, 04/16/92

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.