Issue Date: November 22, 1995
Revision Date: October 18, 2002
OPW Fuel Management Systems
(originally listed as Petro Vend, Inc.)
Petrosentry TLD III, SiteSentinel Smart Module and Vapor Sensor
Out-of-Tank Product Detector (Vapor-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Metal oxide semiconductor |
Test Results
Petrosentry TLD III
Benzene | 2-methylbutane | |
---|---|---|
Detection time (sec) | 5 | 16 |
Fall time (min:sec) | 4:12 | 0:42 |
Lower detection limit (ppm) | 12.5 | 12.5 |
SiteSentinel Smart Module and Vapor Sensor
Unleaded Gasoline | Synthetic Gasoline | JP-4 Jet Fuel | |
---|---|---|---|
Detection time (sec) | 5 | 7 | 10 |
Fall time (min:sec) | 6:30 | 3:35 | 4:26 |
Lower detection limit (ppm) | 10 | 10 | 10 |
Specificity Results (in addition to above for Petrosentry TLD III)
Activated: n-hexane, toluene, n-butane, isobutane, 2-methylpentane.
Specificity Results (in addition to above for SiteSentinal Smart Module and Vapor Sensor)
Activated: n-hexane, toluene, xylene(s).
Manufacturer's specifications
Petrosentry TLD III maximum wire distance: 500 ft using 18 AWG
- OPW Fuel Management Systems
6900 Santa Fe Dr.
Hodgkins, IL 60525
Tel: (708) 485-4200
URL: www.opwglobal.com/opw-fms - Evaluator: Carnegie Mellon Research Institute
Tel: (412) 268-3495
Date of Evaluation: 03/26/91, 04/16/92
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.