Issue Date: November 22, 1995
Revision Date: March 10, 2000
PermAlert
TankWatch Models PHM10, PHMS with Combination Hydrocarbon/Water Probe, Hydrocarbon Probe
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Electrical conductivity |
Test Results
Unleaded Gasoline | Water | |
---|---|---|
Combination Hydrocarbon/Water Probe | ||
Response time (min) | 0.30 | <1 |
Recovery time (min) | 1.97 | 1.68 |
Product activation height (cm) | 0.18 | 0.80 |
Lower detection limit (cm) | 0.56 | 1.93 |
Hydrocarbon Probe | ||
Response time (min) | 0.25 | |
Recovery time (min) | 2.33 | |
Product activation height (cm) | 0.17 | |
Lower detection limit (cm) | 0.38 |
Specificity Results (in addition to above)
Activated: synthetic gasoline, diesel, heating oil #2
Comments
Sensors are reusable.
Hydrocarbon probe is not activated by water.
Hydrocarbon/water probe does not discriminate between gasoline and water.
- PermAlert
6410 W. Howard St.
Niles, IL 60714
Tel: (847) 966-2235
Email: marketing@permalert.com
URL: www.permalert.com - Evaluator: Carnegie Mellon Research Institute
Tel: (412) 268-3495
Date of Evaluation: 06/16/92
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.