Issue Date: November 22, 1995
Revision Date: March 10, 2000

PermAlert

PAL-AT Models AT20C, AT50C, AT40K with AGW Sensor Cable, TFH Hydrocarbon Sensor Cable

Out-of-Tank Product Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Impedance change

Test Results

  Unleaded Gasoline
  1/3 MER* 2/3 MER MER
AGW Sensor Cable 1348 ft. 2644 ft. 3982 ft.
Response time (min) 9.92 6.25 21.28
Recovery time (min) 1.0 1.0 1.0
Product activation height (cm) 2.03 1.13 5.00
Detection length (cm) 116.3 64.8 286.1
Lower detection limits (cm)
Product activation height N/D* N/D 5.1
Detection length N/D N/D 295.6
  Unleaded Gasoline
  1/3 MER 2/3 MER MER
TFH Hydrocarbon Sensor Cable** 1368 ft. 2685 ft. 4046 ft.
Response time (min) 3.40 7.48 16.21
Product activation height (cm) 0.65 1.33 3.53
Detection length (cm) 27.7 56.8 150.4
Lower detection limits (cm)
Product activation height N/D N/D 3
Detection length N/D N/D 152.9

*See glossary.

** California regulations require sensors to be tested annually to verify proper operation. The detector is not reusable and must be replaced after contact with hydrocarbons.

Specificity Results (in addition to above)

Activated: synthetic gasoline, diesel, heating oil #2, water (AGW Sensor Cable only).

Comments

System can monitor interstitial spaces.
Evaluations also covered quantitative leak location.
AGW Sensor Cable is reusable.
TFH Hydrocarbon Sensor Cable is not reusable.
Lower detection limit is calculated at MER only. Cable is assumed to be equally or more sensitive at shorter lengths.

  • PermAlert
    6410 W. Howard St.
    Niles, IL 60714
    Tel: (847) 966-2235
    Email: marketing@permalert.com
    URL: www.permalert.com
  • Evaluator: Carnegie Mellon Research Institute
    Tel: (412) 268-3495
    Date of Evaluation: 01/17/92, 02/11/92

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.