Issue Date: November 22, 1995
Revision Date: March 20, 2003
Sound Products Manufacturing, Inc.
(originally listed as USTest, Inc.)
UST 2000/LL
Volumetric Tank Tightness Test Method (Underfill)
USTest, Inc., no longer supports the use of this method *
Certification | Leak rate of 0.1 gph with PD = 98.12% and PFA = 1.88%. |
---|---|
Leak Threshold | 0.05 gph. A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds this threshold. |
Applicability | Gasoline, diesel, aviation fuel, water, kerosene. Other liquids may be tested after consultation with the manufacturer. |
Tank Capacity | Maximum of 15,000 gallons. Tank must be between 65% and 95% full. |
Waiting Time | Ranges from 3 to 12 hours between delivery and testing. Testing may begin when the rate of product temperature change does not exceed 0.1°F per hour. There must be no dispensing or delivery during waiting time. |
Test Period | Minimum of 2 hours. Test data are acquired and recorded by system's computer, which does a regression analysis to determine the leak rate. An ultrasonic device is used to measure changes in product level. There must be no dispensing or delivery during test. |
Temperature | Average for product is determined from the measurement of the change in the speed of sound. |
Groundwater | Depth to groundwater in tank excavation backfill must be determined. If groundwater is above bottom of tank, product level must be adjusted to provide a minimum net pressure of 1 psi at bottom of tank during test. (There must be a difference of at least 37 inches between groundwater level and product level to provide a net pressure of 1 psi at bottom of tank during test.) |
Calibration | Temperature sensors and probes must be checked annually and, if necessary, calibrated in accordance with manufacturer's instructions. |
Comments | Not evaluated using manifolded tank systems. * USTest Inc. has requested removal of the 2000/LL equipment from the NWGLDE List and discourages the use of this method due to software security and data integrity problems. |
- Sound Products Manufacturing, Inc.
435 Industrial Parkway
Lafayette, LA 70508
Tel: (337) 235-1184 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 06/09/94
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.