Issue Date: November 22, 1995
Revision Date: August 23, 1999
Universal Sensors and Devices, Inc.
Leak Alert System Models LAV-100, LA-01, LA-02, LA-04, LA-X4, LA-08, CATLAS with LAVS-1 MOS Vapor Sensor
Out-Of-Tank Product Detector (Vapor-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Metal oxide semiconductor |
Test Results
Unleaded Gasoline | Synthetic Gasoline | JP-4 Jet Fuel | |
---|---|---|---|
Detection time (sec) | 31 | 40 | 42 |
Fall time (min:sec) | 4:43 | 4:25 | 4:30 |
Lower detection limit (ppm) | 100 | N/D* | N/D |
*See glossary
Specificity Results (in addition to above):
Activated: n-hexane, toluene, xylene(s).
- Universal Sensors and Devices, Inc.
9205 Alabama Ave., Unit C
Chatsworth, CA 91311
Tel: (800) 899-7121, (818) 998-7121 - Evaluator: Carnegie Mellon Research Institute
Tel: (412) 268-3495
Date of Evaluation: 06/01/94
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.