Issue Date: February 6, 2015
Veeder-Root
8601 Series and 8601 Series Consoles Monitoring Systems with CSLD
Continuous In-Tank Leak Detection Method (Continuous Automatic Tank Gauging)
Certification | Leak rate of 0.2 gph with PD = 100% and PFA = 0% | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Leak Threshold |
|
||||||||||||||||||
Applicability | Gasoline, diesel, aviation fuel, fuel oil #4, solvents, biodiesel blends B6-B20 meeting ASTM D7467, biodiesel B100 meeting ASTM D6751* Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer. *NWGLDE Listings apply to leak detection functionality only and not material compatibility - see Disclaimer. |
||||||||||||||||||
Tank Capacity | Maximum of 43,722 gallons for single tanks and for up to 3 tanks manifolded together. The minimum product level required to conduct a test is 15% full. | ||||||||||||||||||
Throughput | Monthly maximum of 235,000 gallons | ||||||||||||||||||
Waiting Time | Minimum of 3 hours stabilization time is allowed between delivery and data collection | ||||||||||||||||||
Test Period | Data collection time ranges from 25 to 28 days. Data sampling frequency is once per minute. System collects data at naturally occurring product levels without interfering with normal tank operation, and discards data from unstable periods when system performs test. |
||||||||||||||||||
Temperature | Average for product is determined by a probe which contains 5 thermistors. At least two thermistors must be submerged in product during test | ||||||||||||||||||
Water Sensor | Must be used to detect water ingress. Minimum detectable water level in the tank is 0.75 inch. Minimum detectable change in water level is 0.08 inch. |
||||||||||||||||||
Calibration | Thermistors and probe must be checked and, if necessary, calibrated in accordance with manufacturer's instructions. | ||||||||||||||||||
Comments | System reports a leak rate and a "pass" or "fail" result. Evaluated using both single and manifolded tank systems with probes in each tank. For valid monthly testing, a conclusive test report must be produced for each tank every month. System warns operator if there are no “ passing” tests completed during the month. |
- Veeder-Root
125 Powder Forest Dr.
Simsbury, CT 06070-2003
Tel: (860) 651-2700
Email: info@veeder.com
URL: www.veeder.com/us - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 06/29/98 (Rev. 4/17/02) 10/26/07, 02/29/08(water sensor), 10/03/14
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.