Issue Date: November 22, 1995
Revision Date: December 6, 2002

Agar Corp.

LEAKWISE Groundwater Monitor
ID-220 Series Hydrocarbon on Water Detector System

Out-of-Tank Product Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Radio frequency (RF) attenuation

Test Results

  Unleaded Gasoline Synthetic Gasoline
Detection time (sec) <1 <1
Fall time (sec) <1 <1
Lower detection limits (cm)
"Standard" setting 0.16 0.32
"Sensitive" setting 0.03 0.03

Specificity Results

Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s), water.

Manufacturer's specifications

Operating range:

Resolution 0.5 mm of hydrocarbon on water or brine
Variation Groundwater fluctuation of +/- 1 meter standard (larger variations optional)
Oil thickness 0.3 - 25 mm optional (higher ranges available)
Temperature 0 - 70 degrees C (higher available)

Comments

Sensors are reusable.

Color coded signal lights indicate the presence of air, water, and hydrocarbon liquid when activated (yellow, green, and red, respectively).

  • Agar Corp.
    5150 Tacoma Drive
    Houston, TX 77041
    Tel: (832) 476-5100
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 11/15/91

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.