Issue Date: April 18, 1997
Revision Date: October 27, 2005

Sequence Controls, Inc.

(originally listed as Armstrong Monitoring, Corp.)

AMC 5100
Vapor Sensor AMC F4000

Out-of-Tank Product Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Metal oxide semiconductor

Test Results

  Benzene
Detection time (sec) 10
Fall time (min:sec) 04:02
Lower detection limit (cm) 300

Comments

Sensors are reusable.

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.