Issue Date: April 18, 1997
Revision Date: September 11, 1998
Bell Avon, Inc.
VIGILANT Leak Detection System
Continuous Interstitial Tank System Monitoring Method (Pressure/Vacuum)
Certification | Leak rate of 0.1 gph with PD = 100% and PFA = 0%. |
---|---|
Leak Threshold | System alarms when changes in interstitial vacuum exceed a predetermined change in slope versus time curve. |
Applicability | Gasoline, diesel, aviation fuel, fuel oil #4, waste oil. Other liquids may be tested which are compatible with flexible liner after consultation with the manufacturer. |
Tank Capacity | Maximum of 15,000 gallons based on interstitial volume resulting when flexible liner is properly fitted and held in position against rigid tank wall. No minimum product level during test. |
Waiting Time | Minimum of 20 minutes between delivery and testing. |
Test Period | Minimum of 40 minutes. |
Comments | System is located within the interstitial space between a properly fitted and installed flexible liner inside a rigid tank. State Waterboard staff are currently evaluating the applicability of this method in satisfying the performance standards for continuous vacuum/pressure monitoring systems required by Assembly Bill 2481 (Chapter 6.7, Health and Safety Code, section 25290.1). Listings will be updated once a determination has been made. |
- Bell Avon, Inc.
1200 Martin Luther King, Jr. Blvd.
Picayune, MS 39466-5427
Tel: (601) 799-1217 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 11/16/95
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.