Issue Date: November 22, 1995
Revision Date: May 7, 2007
Chapman Engineering
(originally listed as Environmental Fuel Systems, Inc.)
Fuel Finder Version IV
Out-of-Tank Product Detector (Vapor-Phase)
Detector
Output Type | Quantitative |
---|---|
Sampling Frequency | Intermittent |
Operating Principle | Adsorption sampling |
*California regulations require vadose zone vapor monitoring to be continuous. This sensor does not meet the criteria.
Test Results
Benzene | 2-Methylbutane | |
---|---|---|
Accuracy (%) [Avg. Reading] | 106.8 [1647 ppm] | 122.7 [1380 ppm] |
Bias (%) | 64.5 | 38.2 |
Precision (%) | 22.3 | 53.2 |
Detection time | N/A* | N/A |
Lower detection limit (ppm) | 77 | 116 |
Specificity Results
Percentages | |
---|---|
Benzene | 147.7 |
n-butane | 90.7 |
n-hexane | 55.7 |
Isobutane | 51.1 |
2-methylpentane | 143.7 |
Toluene | 66.5 |
- Chapman Engineering
P.O. Box 1305
213 Commerce Street
Boerne, TX 78066
Tel: (800) 375-7747 - Evaluator: Carnegie Mellon Research Institute
Tel: (412) 268-3495
Date of Evaluation: 04/20/93
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.