Issue Date: January 11, 2001
Revision Date: December 21, 2010
Containment Solutions, Inc.
(originally listed as Fluid Containment and O/C Tanks)
FOVF 600B, FOVF 600S Non-Discriminating Sensors for High Level Overfill (Brass, Steel); FCBS 700 Non-Discriminating Sensor for Collars, Bulkheads, Sumps; FDAS 710 Non-Discriminating Sensor for Dry Annular Spaces; FHRB 810 Non-Discriminating Sensor for Reservoirs
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Float switch |
Test Results
Discriminating Sensors | Unleaded Gasoline | Diesel* | Water |
---|---|---|---|
FOVF 600B, FOVF 600S (Overfill) | |||
Lower Detection Limit (in) | 3.32 | 3.26 | 3.18 |
Precision-Standard Deviation (in) | 0.0051 | 0.0025 | 0.0037 |
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
FCBS 700 (Collars, Bulkheads, Sumps) | |||
Lower Detection Limit (in) | 0.99 | 0.97 | 0.87 |
Precision-Standard Deviation (in) | 0.0040 | 0.0027 | 0.0043 |
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
FDAS 710 (Dry Annular Spaces) | |||
Lower Detection Limit (in) | 0.44 | 0.43 | 0.42 |
Precision-Standard Deviation (in) | 0.0025 | 0.0041 | 0.0031 |
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
FHRB 810 (Reservoirs - Low level float) | |||
Lower Detection Limit (in) | 2.57 | 2.53 | 2.31 |
Precision-Standard Deviation (in) | 0.0042 | 0.111 | 0.0042 |
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
FHRB 810 (Reservoirs - High level float) | |||
Lower Detection Limit (in) | 13.31 | 13.24 | 13.01 |
Precision-Standard Deviation (in) | 0.0080 | 0.0061 | 0.0042 |
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
*This evaluation determined the sensors' responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
Comments
Control panel models:
CPF 1, CPF 2, CPF 3, CPF 4 for liquid level sensors;
CPI 1D, CPI 1H, CPI 1N inventory control for liquid level sensors and 1 tank;
CPD 1, CPD 2, CPD 4 for discriminating liquid level sensors;
CPI 4 inventory control for liquid level sensors and up to 4 tanks;
BOMC battery operated control cap for liquid level sensors;
CCF 1DA battery operated control cap for dry annulus monitoring;
CCF 2 battery operated control cap for hydrostatic reservoir monitoring.
- Containment Solutions, Inc
5150 Jefferson Chemical
Conroe, TX 77301-6834
Tel: (800) 628-2657 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 06/11/99
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.