Issue Date: November 22, 1995
Revision Date: May 23, 2007

Estabrook EZY CHEK Systems

(originally listed as Horner EZY CHEK)

EZY-Chek II Automatic Line Leak Detector

Line Tightness Test Method

Certification Leak rate of 0.1 gph with PD = 99.0% and PFA = 1%.
Leak Threshold 0.05 gph.
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel, fuel oil #4.
Other liquids may be tested after consultation with the manufacturer.
Specification System tests fiberglass and steel pipelines.
Tests are conducted at 150% operating pressure.
Pipeline Capacity Maximum of 129 gallons.
Waiting Time None between delivery and testing.
None between dispensing and testing.
Test Period Minimum of 2 hours.
Data are collected every 30 seconds.
Testing period consists of a monitor mode and test mode.
Data are collected in monitor mode until two consecutive 15 minute records are within 0.01 gallon of each other. Then an additional 15 minutes is required in monitor mode before start of test mode.
Data are collected in test mode for 1 hour, 7 minutes.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
Calibration Sensors must be calibrated in accordance with manufacturer's instructions before each test.
  • Estabrook EZY CHEK Systems
    1505 Woodside Ave.
    Essexville, MI 48732
    Tel: (989) 891-9868
    E-mail: sales@ezychek.com
    URL: www.ezychek.com
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 07/13/92

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.