Issue Date: November 22, 1995
Revision Date: November 14, 1997
FCI Environmental, Inc.
Analog Hydrocarbon Probe AHP-100, Digital Hydrocarbon Probe DHP-100
Out-Of-Tank Product Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Fiber optic chemical sensor |
Test Results
Unleaded Gasoline | Synthetic Gasoline | |
---|---|---|
Detection time (min) | <8 | <8 |
Fall time (min) | <5 | <5 |
Lower detection limit (cm) | <0.01 | <0.01 |
Specificity Results (in addition to above)
Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s).
Comments
Sensors are reusable.
- FCI Environmental, Inc.
1181 Grier Dr., Bldg. B
Las Vegas, NV 89119
Tel: (800) 510-3627 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 01/15/94
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.