Issue Date: November 22, 1995
Revision Date: November 14, 1997

FCI Environmental, Inc.

Analog Hydrocarbon Probe AHP-100, Digital Hydrocarbon Probe DHP-100

Out-Of-Tank Product Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Fiber optic chemical sensor

Test Results

  Unleaded Gasoline Synthetic Gasoline
Detection time (min) <8 <8
Fall time (min) <5 <5
Lower detection limit (cm) <0.01 <0.01

Specificity Results (in addition to above)

Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s).

Comments

Sensors are reusable.

  • FCI Environmental, Inc.
    1181 Grier Dr., Bldg. B
    Las Vegas, NV 89119
    Tel: (800) 510-3627
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 01/15/94

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.