Issue Date: November 22, 1995
Revision Date: April 18, 1997

FDR Services, Inc.

GasPak Vapor Monitoring System

Out-of-Tank Product Detector (Vapor-Phase)

Detector

Output Type Quantitative
Sampling Frequency Intermittent
Operating Principle Product permeable detector

*California regulations require vadose zone vapor monitoring to be continuous. This sensor does not meet the criteria.

Test Results (averages of multiple concentrations)

  Benzene Heptane,
3-methy
Hexane Iso-octane
Accuracy (%) 103 102 107 103
Bias (%) -1 1 2 1
Precision (%) 2 2 4 3
Lower detection limit (ppm) 1 1 1 1
Specificity (%) 100 100 102 101
  Pentane,
2,4-dimethyl
Pentane,
2,3,4-trimethyl
Toluene M-xylene
Accuracy (%) 105 104 104 99
Bias (%) 1 1 1 -6
Precision (%) 3 3 3 4
Lower detection limit (ppm) 3 1 1 4
Specificity (%) 101 100 100 94

Specificity Results

See results above.

Comments

Detection times were not directly measured. However, evaluator states, "experiential evidence predicts that the detector response will reach 'alarm' conditions (30% of maximum fresh fuel response) at a distance of 5 meters in slightly over one day."

Each cartridge is used once, then replaced by another.

GasPak is produced and analyzed by Fayette Environmental Services, Inc., with exclusive marketing and implementation rights assigned to FDR Services, Inc.

  • FDR Services, Inc.
    219 North Main St., Suite 202
    Bryan, TX 77803
    Tel: (800) 337-5325
  • Evaluator: David G. Bray, Ph.D.
    University of Missouri - Columbia
    Tel: (573) 882-2439
    Date of Evaluation: 07/27/94

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.