Issue Date: November 22, 1995
Revision Date: April 4, 2016
FE Petro, Inc.
STP-MLD-D Pipeline Leak Detector
Automatic Mechanical Line Leak Detector
Certification | Leak rate of 3.0 gph with PD = 100% and PFA = 0%. |
---|---|
Leak Threshold | 2.0 gph. A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold. |
Applicability | Diesel |
Specification | System tests fiberglass and steel pipelines. Tests are conducted at operating pressure. |
Pipeline Capacity | Maximum for rigid system is 341 gallons. |
Waiting Time | None between delivery and testing. None between dispensing and testing |
Test Period | Average response time is 1 minute. |
System Features | Permanent installation on pipeline. Automatic testing of pipeline. Preset threshold. Single test to determine if pipeline is leaking. Restricted flow to dispenser if leak is declared. |
Calibration | Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions. |
Comments | Evaluations determined that the STP-MLD-D Pipeline Leak Detector will operate correctly with a range of diesel from 100% diesel to 100% Ultrazol 9888, OTR 8843G, and OTR 8332G. |
- Franklin Fueling Systems
3760 Marsh Road
Madison, WI 53718
Tel: (800) 225-9787
Email: info@franklinfueling.com
URL: www.franklinfueling.com - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 04/30/94, 03/30/16
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.