Issue Date: August 15, 2022

Franklin Fueling Systems

Franklin Fueling Systems EVO 200, EVO 400, EVO600, and EVO6000 with FMP-DIS-U Discriminating Interstitial Sensor and FMP-EIS-U Electro-Optical Interstitial Sensor

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Float switch

Test Results

  Unleaded Gasoline Diesel* Waste oil Water E85
FMP-DIS-U
Detection time (min) <1 <1 <1 <1 <1
Fall time (min) <1 <1 <1 <1 <1
Threshold level (in) 0.4293 0.4397 0.4208 0.4594 0.4240
FMP-EIS-U
Detection time (min) <1 <1 <1 <1 <1
Fall time (min) <1 <1 <1 <1 <1
Threshold level (in) 0.4478 0.4430 0.4317 0.4566 0.4507

Applicability

California Code of Regulations require a written statement of compatibility for systems containing products other than those used in this evaluation.

Comments

Sensors can be removed, cleaned and reinstalled if an alarm is triggered or if the sensor is periodically tested.

  • Franklin Fueling Systems
    3760 Marsh Road
    Madison, WI 53718
    Tel: (800) 225-9787
    E-Mail: info@franklinfueling.com
    URL: www.franklinfueling.com
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 05/02/2017, 11/8/2018

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.