Issue Date: August 3, 2015
Franklin Fueling Systems
Incon TS-1001/2001, TS-5, TS-550, TS-5000, TS-550 evo, and TS-5000 evo with FMP-HFS Horizontal Float Switch, FMP-HLS High Level Float Switch, FMP-HIS Hydrostatic Interstitial Float Sensor, and FMP-HIS-XL Hydrostatic Interstitial Float Sensor
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Float switch |
Test Results
Unleaded Gasoline | Diesel* | Waste oil | Water | E85 | |
---|---|---|---|---|---|
FMP-HFS | |||||
Detection time (min) | < | < | < | < | < |
Fall time (min) | <1 | <1 | <1 | <1 | <1 |
Threshold level (in) | 0.3890 | 0.3759 | 0.3890 | 0.3091 | 0.3975 |
FMP-HLS | |||||
Detection time (min) | <1 | <1 | <1 | <1 | <1 |
Fall time (min) | <1 | <1 | <1 | <1 | <1 |
Threshold level (in) | 2.1369 | 2.0976 | 2.0882 | 2.0358 | 2.1350 |
FMP-HIS | |||||
Detection time (min) | <1 | ||||
Fall time (min) | <1 | ||||
Threshold Level | |||||
Low level (in) | 1.0699 | ||||
High level (in) | 7.4890 | ||||
FMP-HIS-XL | |||||
Detection time (min) | <1 | ||||
Fall time (min) | <1 | ||||
Threshold Level | |||||
Low level (in) | 1.0061 | ||||
High level (in) | 10.9546 |
Manufacturer and evaluator claim that sensors will respond to any liquid. Evaluations determined these sensors' responses to the liquids shown above.
*Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
Comments
Sensors can be removed, cleaned and reinstalled if an alarm is triggered or if the sensor is periodically tested. The FMP-HIS, FMP-HIS-XL, FMP-HLS, and FMP-HFS sensors are identical in operation and communication to Franklin Fueling System's TSP-HIS, TSP-HIS-XL, TSP-HLS, and TSP-HFS sensors. The FMP-HIS, FMP-HIS-XL, FMP-HLS, and FMP-HFS sensors can connect to any INCON console with no software or setup changes. FMP-HIS, FMP-HIS-XL, FMP-HLS, and FMP-HFS sensors can be distinguished from TSP-HIS, TSP-HIS-XL, TSP-HLS, and TSP-HFS sensors by the part number on the label that begins with "FMP" instead of "TSP." The TSP-HIS, TSP-HIS-XL, TSP-HLS, TSP-HFS, FMP-HIS, FMP-HIS-XL, FMP-HLS, and FMP-HFS sensors appear as the same device from the automatic tank gauge.
- Franklin Fueling Systems
3760 Marsh Road
Madison, WI 53718
Tel: (800) 225-9787
E-Mail: info@franklinfueling.com
URL: www.franklinfueling.com - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 04/02/15
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.