Issue Date: August 07, 2017
Franklin Fueling Systems
Franklin Fueling Systems EVO400, EVO200 with FMP-DIS-U Discriminating Interstitial Sensor and FMP-EIS-U Electro-Optical Interstitial Sensor
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Float switch |
Test Results
FMP-DIS
Unleaded Gasoline | Diesel | Waste Oil | Water | E85 | |
---|---|---|---|---|---|
Detection time (min) | <1 | <1 | <1 | <1 | <1 |
Fall time (min) | <1 | <1 | <1 | <1 | <1 |
Threshold Level (in) | 0.4293 | 0.4397 | 0.4208 | 0.4594 | 0.4240 |
FMP-EIS
Unleaded Gasoline | Diesel | Waste Oil | Water | E85 | |
---|---|---|---|---|---|
Detection time (min) | <1 | <1 | <1 | <1 | <1 |
Fall time (min) | <1 | <1 | <1 | <1 | <1 |
Threshold Level (in) | 0.4478 | 0.4430 | 0.4317 | 0.4566 | 0.4507 |
Manufacturer and evaluator claim that sensors will respond to any liquid. Evaluations determined these sensors' responses to the liquids shown above.
*Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
Comments
Sensors can be removed, cleaned and reinstalled if an alarm is triggered or if the sensor is periodically tested.
The FMP-DIS sensor uses two conductive pins to detect whether the liquid is water or fuel. When tested in three mixtures of water/E85 (i.e., 20%/80%; 30%/70%; and 70%/30%), the FMP-DIS sensor went into alarm when subjected to the upper and lower layers of water/E85. For the upper layer containing hydrocarbon, the DIS sensor indicated a product or alarm as designed. For the lower layer of liquid, the DIS sensor indicated a “water” alarm.
- Franklin Fueling Systems
3760 Marsh Road
Madison, WI 53718
Tel: (800) 225-9787
E-Mail: info@franklinfueling.com
URL: www.franklinfueling.com - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 05/02/2017
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.