Issue Date: August 07, 2017

Franklin Fueling Systems

Franklin Fueling Systems EVO400, EVO200 with FMP-HIS-U Hydrostatic Interstitial Float Sensor, and FMP-HIS-XL-U Hydrostatic Interstitial Float Sensor

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Float switch

Test Results

FMP-HIS

  Brine
Detection time (min) <1
Fall time (min) <1
Threshold Level (in)
Low level (in) 1.0167
High level (in) 7.3218

FMP-HIS-X

  Brine
Detection time (min) <1
Fall time (min) <1
Threshold Level (in) 1.0678
Low level (in) 0.9895
High level (in) 10.8398

Manufacturer and evaluator claim that sensors will respond to any liquid. Evaluations determined these sensors' responses to the liquids shown above.

*Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.

Comments

Sensors can be removed, cleaned and reinstalled if an alarm is triggered or if the sensor is periodically tested.

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.