Issue Date: November 22, 1995
Revision Date: November 14, 1997
Gems Sensors Inc.
(originally listed as IMO Industries, Inc.)
Gems Smartwell Portable Monitor Model WPM-535 with Groundwater Probe Model WP-535
Out-of-Tank Product Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Intermittent |
Operating Principle | Conductive polymer |
Test Results
Unleaded Gasoline | Synthetic Gasoline | |
---|---|---|
Detection time (min:sec) | 09:31 | 07:05 |
Fall time (min:sec) | 55:42 | 17:04 |
Lower detection limit (cm) | 0.04 | 0.08 |
Specificity Results
Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s).
Comments
Sampling frequency is designated as "intermittent" because polymer strip is permanently mounted in monitoring well, while monitor is a hand held unit which is periodically connected to sensor.
Sensors are reusable.
- Gems Sensors Inc.
1 Cowles Rd.
Plainville, CT 06062-1198
Tel: (800) 378-1600 - Evaluator: Carnegie Mellon Research Institute
Tel: (412) 268-3495
Date of Evaluation: 04/22/93
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.