Issue Date: November 22, 1995
Revision Date: June 5, 2002
Gems Sensors, Inc.
(originally listed as Warrick Controls, Inc.)
Model 5700 Meter with PVP-2 Sensor
Out-Of-Tank Product Detector (Vapor-Phase)
Detector
Output Type | Quantitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Adsistor |
Test Results
Unleaded Gasoline | Synthetic Gasoline | JP-4 jet fuel | |
---|---|---|---|
Accuracy (%) | 25.4 | -100.0 | 157.1 |
Bias (%) | 14.4 | -100.0 | 108.3 |
Precision (%) | 7.6 | N/D* | 20.4 |
Detection time (min) | >60 | N/A* | >60 |
Fall time (min) | 38 | N/A* | >60 |
Lower detection limit (ppm) | 1353.3 | N/D | N/D |
Specificity Results
Not Activated: n-hexane, toluene, xylene(s).
- Gems Sensors, Inc.
1 Cowles Rd.
Plainville, CT 06062-1198
Tel: (800) 378-1600 - Evaluator: Carnegie Mellon Research Institute
Tel: (412) 268-3495
Date of Evaluation: 09/10/91
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.