Issue Date: November 22, 1995
Revision Date: June 5, 2002

Gems Sensors, Inc.

(originally listed as Warrick Controls, Inc.)

Model 5700 Meter with PVP-2 Sensor

Out-Of-Tank Product Detector (Vapor-Phase)

Detector

Output Type Quantitative
Sampling Frequency Continuous
Operating Principle Adsistor

Test Results

  Unleaded Gasoline Synthetic Gasoline JP-4 jet fuel
Accuracy (%) 25.4 -100.0 157.1
Bias (%) 14.4 -100.0 108.3
Precision (%) 7.6 N/D* 20.4
Detection time (min) >60 N/A* >60
Fall time (min) 38 N/A* >60
Lower detection limit (ppm) 1353.3 N/D N/D

*See glossary.

Specificity Results

Not Activated: n-hexane, toluene, xylene(s).

  • Gems Sensors, Inc.
    1 Cowles Rd.
    Plainville, CT 06062-1198
    Tel: (800) 378-1600
  • Evaluator: Carnegie Mellon Research Institute
    Tel: (412) 268-3495
    Date of Evaluation: 09/10/91

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.