Issue Date: April 18, 1997
Revision Date: August 12, 2015
Franklin Fueling Systems
(Originally listed as INCON Intelligent Controls, Inc.)
Tank Sentinel TS-1000EFI , TS-1001/TS-2001, and TS-5xxx Series with TSP-HIS BriteSensor; Tank Sentinel TS-1000/TS-2000, TS-1001/TS-2001, and TS-5xxx Series with TSP-HLS Standard Sensor, TSP-ULS Standard Sensor and TSP-UHS Standard Sensor
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Magnetic switch |
Test Results
50% by weight ethylene glycol in water |
30% by weight calcium chloride in water |
|||
---|---|---|---|---|
High* | Low* | High | Low | |
TSP-HIS BriteSensor | ||||
Response time (min:sec) | 17:41 | 16:47 | 17:28 | 16:56 |
Recovery time (min) | <1 | <1 | <1 | <1 |
Product activation height (cm) | 19.56 | 2.53 | 19.40 | 2.50 |
Unleaded gasoline | Synthetic gasoline | Diesel*** | Heating oil #2 | Water | E85 | Waste oil | |
---|---|---|---|---|---|---|---|
TSP-HLS Standard Sensor | |||||||
Detection time (min:sec) | 10:09 | 10:14 | 09:55 | 10:25 | 09:25 | -- | -- |
Fall time (min) | <1 | <1 | <1 | <1 | <1 | -- | -- |
Product activation height (cm) | 5.64 | N/D** | N/D | N/D | N/D | -- | -- |
Lower Detection limit (cm) | 5.03 | 5.03 | 4.93 | 5.17 | 4.77 | -- | -- |
TSP-ULS Standard Sensor | |||||||
Detection time (min:sec) | 03:50 | 03:49 | 03:50 | 03:41 | 03:34 | <1 | <1 |
Fall time (min) | <1 | <1 | <1 | <1 | <1 | <1 | <1 |
Product activation height (cm) | 2.70 | N/D | N/D | N/D | N/D | 2.59 | -- |
Lower Detection limit (cm) | 1.93 | 1.97 | 1.93 | 1.80 | 1.80 | 2.58 | 1.17 |
TSP-UHS Standard Sensor | |||||||
Detection time (min:sec) | 03:50 | 03:49 | 03:50 | 03:41 | 03:34 | <1 | <1 |
Fall time (min) | <1 | <1 | <1 | <1 | <1 | <1 | <1 |
Product activation height (cm) | 2.70 | N/D | N/D | N/D | N/D | 2.96 | -- |
Lower Detection limit (cm) | 1.93 | 1.97 | 1.93 | 1.80 | 1.80 | 2.95 | 1.22 |
*The "high" and "low" refer to high and low level alarm points of hydrostatic sensors.
**See glossary.
***This evaluation determined the sensor's responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined, but would be expected to be very similar to the diesel responses.
Comments
TSP-HIS BriteSensor is intended to monitor level of either ethylene glycol or calcium chloride solutions in interstitial or annular space of a double-walled tank. Activates if any significant gain or loss of solution occurs.
Comparison of Tank Sentinel TS-1001/TS-2001 and TS-5xxx series consoles with Tank Sentinel TS-1000(including EFI)//TS-2000 series consoles showed comparable results when evaluated with representative sensors.
TSP-UHS is the same as the TSP-ULS sensor except that the float has been inverted so that it may be used to monitor the brine reservoir of containment sumps. An alarm condition will occur when the fluid level drops below the end of the sensor.
Sensors are reusable.
- Franklin Fueling Systems
3760 Marsh Road
Madison, WI 53718
Tel: (800) 225-9787
Email: info@franklinfueling.com
URL: www.franklinfueling.com - Evaluator: Carnegie Mellon Research Institute
Tel:(412) 268-3495
Dates of Evaluation: 03/20/95, 01/30/96
Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 4/1/08, 11/20/10, 10/18/11
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.