Issue Date: November 22, 1995
Revision Date: August 23, 1999
Mallory Controls
Pollulert Probes MD221G/T, MD221G/TRA, MD241R, MD241RRA, MD241G, MD241GRA
Out-Of-Tank Product Detector (Liquid-Phase)
Mallory Controls no longer produces, services, or supports the use of this method.
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Electrical conductivity |
Test Results
Unleaded Gasoline | Synthetic Gasoline | JP-4 Jet Fuel | |
---|---|---|---|
MD221G/T, MD221G/TRA* | |||
Detection time (sec) | 4 | 7 | 2 |
Fall time (sec) | 3 | 4 | 4 |
Lower detection limit (cm) | 0.08-0.32 | 0.08-0.32 | 0.08-0.32 | MD241R, MD241RRA, MD241G, MD241GRA** |
Detection time (sec) | 2 | 2 | 1 |
Fall time (sec) | 1 | 2 | 2 |
Lower detection limit (cm) | 0.16-0.32 | 0.16-0.32 | 0.16-0.32 |
*Evaluation was conducted using probe FD221G/TRA.
**Evaluation was conducted using probe FD241R.
Specificity Results
Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s).
Comments
According to manufacturer, probes beginning with "MD" have identical performance as older probes beginning with "FD."
Sensors are reusable.
Manufacturer no longer produces, services, or supports this equipment.
- Manufacturer's previously listed contact information is no longer valid.
- Evaluator: Radian Corp.
Tel: (512) 454-4797
Date of Evaluation: 07/08/91
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.