Issue Date: November 22, 1995
Revision Date: April 18, 1997
Mallory Controls
Pollulert Probes MD221V, MD221VRA, MD210V, MD210VRA
Out-Of-Tank Product Detector (Vapor-Phase)
Mallory Controls no longer produces, services, or supports the use of this method.
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Adsistor |
Test Results
Unleaded Gasoline | Synthetic Gasoline | JP-4 Jet Fuel | |
---|---|---|---|
Detection time (sec) | 91 | 65 | 86 |
Fall time (min:sec) | 5:39 | 4:23 | 9:38 |
Lower detection limit (ppm) | 10 to 100 | 10 to 500 | 10 to 50 |
Specificity Results (in addition to above)
Activated: toluene, xylene(s).
Not Activated: n-hexane.
Comments
Evaluation was conducted using probe FD221V.
According to manufacturer, probes beginning with MD have identical performance as older probes beginning with FD.
Manufacturer no longer produces, services, or supports this equipment.
- Manufacturer's previously listed contact information is no longer valid.
- Evaluator: Radian Corp.
Tel: (512) 454-4797
Date of Evaluation: 07/08/91
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.