Issue Date: November 22, 1995
Revision Date: April 18, 1997

One Plus Corp.

Leak Edge
Models 100-3001, 100-4001

Out-of-Tank Product Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Product permeable

Test Results

  Unleaded Gasoline Synthetic Gasoline
Detection time (min:sec) 5:41 5:14
Fall time (min:sec) 30:39 18:36
Lower detection limit (cm) 0.02 0.02

Specificity Results (in addition to above)

Activated: n-hexane, diesel, jet-A fuel, toluene, xylene(s).

Manufacturer's specifications

Operating temperatures: Sensor is -40 degrees C to 74 degrees C; Monitor Module is -20 degrees C to 49 degrees C.

Comments

Sensors are reusable.

  • One Plus Corp.
    3182 McArthur Blvd.
    Northbrook, IL 60062
    Tel: (847) 498-0955
  • Evaluator: Underwriters Laboratories Inc.
    Tel: (847) 272-8800
    Date of Evaluation: 12/17/91

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.