Issue Date: November 7, 2001
Revision Date: August 18, 2005
OPW Fuel Management Systems
(originally listed as Petro Vend, Inc.)
SiteSentinel Controller with Optical Sensor Part #30-3223
Out-of-Tank Product Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Optical (Part #30-3223) |
Test Results
Unleaded gasoline | Diesel | Water | |
---|---|---|---|
Detection time (sec) | <1 | <1 | <1 |
Fall time (sec) | <1 | <1 | <1 |
Lower detection limit (in) | 0.571 | 0.561 | 0.592 |
Specificity Results
Part #3223 works with any liquid.
- OPW Fuel Management Systems
6900 Santa Fe Dr.
Hodgkins, IL 60525
Tel: (708) 485-4200
URL: www.opwglobal.com/opw-fms - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 08/03/00
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.