Ronan Engineering Co.

Ronan Controller Models X76S; X76VS; X76LVC; TRS76; X76ETM, LVCS; X76CTM-N4; X76ETM-4X; X76-4X, -3, -6, -9, -12; X76AST-4X with Ronan Sensor Models LS-3 N.C.; LS-3 N.O.; LS-30; LS-7; HVA; LS-3SS; LS-1

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

float switch

Test Results:

unleaded gasoline

water

LS-3 N.C. (normally closed)

Detection time (sec)

<1

<1

Fall time (sec)

<1

<1

Lower detection limit (cm)

2.77

2.31

LS-3 N.O. (normally open)

 

 

Detection time (sec)

<1

<1

Fall time (sec)

<1

<1

Lower detection limit (cm)

2.31

1.70

LS-30 (high level)

 

 

Detection time (sec)

<1

<1

Fall time (sec)

<1

<1

Lower detection limit (cm)

N/D*

15.24

LS-30 (low level)

 

 

Detection time (sec)

<1

<1

Fall time (sec)

<1

<1

Lower detection limit (cm)

N/D

4.72

LS-7

 

 

Detection time (sec)

<1

<1

Fall time (sec)

<1

<1

Lower detection limit (cm)

1.09

0.81

HVA

 

 

Detection time (sec)

<1

<1

Fall time (sec)

<1

<1

Lower detection limit (cm)

0.84

0.71

*See Glossary

Comments:
Sensors are reusable.
LS-3SS is identical to LS-3 N.C. and LS-3 N.O. except that LS-3SS also tests for methanol and has a stainless steel float.
The only difference between LS-1 and LS-3 is that LS-1 is smaller in diameter.

 

Ronan Engineering Co.

Evaluator:  Ken Wilcox Associates

21200 Oxnard St.

Tel:  (816) 443-2494

Woodland Hills, CA  91367

Date of Evaluation:  02/06/92

Tel: (800) 327-6626

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.