Issue Date: January 11, 2001

Simone Engineering, Inc.

Magnetrol Model 918 Ultrasonic Point Level Switch with ABB Automation Freelance 2000 Control System

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative, non-discriminating
Sampling Frequency Continuous
Operating Principle Electrical conductivity, ultrasonic

Test Results

  Trichloroethylene Acetone Water
Lower detection limit (in) 0.143 0.166 0.164
Detection time (sec) <1 <1 <1
Fall time (sec) <1 <1 <1

Specificity Results

Evaluator claims sensors will respond to any liquid after threshold is exceeded.

Comments

The Magnetrol Model 918 has not been evaluated for application with petroleum hydrocarbons. The sensor has been evaluated specifically for application in water, acetone, and trichloroethylene.
The ABB Automation Freelance 2000 was used to detect the 8 to 16 milliamp change that occurred in the Magnetrol sensor when it became submerged in product. Audible and visual alarms were activated when the sensor indicated that alarm conditions were present.

  • Simone Engineering, Inc.
    2635 45th Street
    Highland, IN 46322-2985
    Tel: (219) 922-6750
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 01/27/00

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.