Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Programs - LG 113

Issue Date: November 22, 1995
Revision Date: August 23, 1999
 

Tidel Engineering, Inc.

Tidel Detector #301-0324-001, #301-0325-001, #301-0326-001, #301-0326-002

OUT-OF-TANK PRODUCT DETECTOR (LIQUID-PHASE)

 

Detector:

Output type

qualitative

Sampling frequency:

continuous

Operating principle:

electrical conductivity

Test Results:

Tidel Detector #301-0324-001, #301-0325-001

 

unleaded gasoline

 

synthetic gasoline

 

JP-4 jet fuel

Detection time (sec)  

2

2

1

Fall time (sec)  

1

2

2

Lower detection limit (cm)

0.16-0.32

0.16-0.32

0.16-0.32

Tidel Detector #301-0326-001, #301-0326-002

 

 

 

Detection time (sec)

4

7

2

Fall time (sec)

3

4

4

Lower detection limit (cm)

0.08-0.32

0.08-0.32

0.08-0.32

Specificity Results (in addition to above):
Activated:  n-hexane, diesel, jet-A fuel, toluene, xylene(s).

Manufacturer's specifications:

Tidel Detector #301-0324-001

Application:

Liquid sensor, water, used in 4" monitoring well.

Sensor:

Magnetism and conductivity pins.

Detection Range :

1/8" floating product on groundwater or 1.5" free product.

Tidel Detector #301-0325-001

Application:

Liquid sensor, water or hydrocarbon used in reservoir, sump or pipeline trench.

Sensor:

Magnetism and conductivity pins.

Detection Range :

1/8" floating product on groundwater or 1.5" free product.

Tidel Detector #301-0326-001

Application:

Liquid sensor, water, used in 2" monitoring well.

Sensor:

Magnetism and conductivity pins.

Detection Range :

1/8" floating product on groundwater or 2.5" free product.

Tidel Detector #301-0326-002

Application:

Liquid sensor, water, used in annulus of double wall steel tanks.

Sensor:

Magnetism and conductivity pins.

Detection Range :

1/8" floating product on groundwater or 2.5" free product.

Comments:
Sensors are reusable.
Lower detection limit has been statistically determined to be within the range specified above.

 

Tidel Engineering, Inc.

Evaluator:  Radian Corp.

2310 McDaniel Dr .

Tel:  (512) 454-4797

Carrollton , TX   75006

Date of Evaluation:  07/08/91

Tel:  (800) 678-7577

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.
For full details, please refer to our expanded "DISCLAIMER" page.

 
 

.