Issue Date: November 22, 1995
Revision Date: April 17, 2003
Tyco Thermal Controls LLC
(originally listed as Raychem Corp.)
TraceTek Alarm and Locator Modules with TT502, TT5000, TT3000 Fuel Sensing Cable
Interstitial Detector (Liquid-Phase) and Liquid-Phase Out-Of-Tank Product Detector
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Electrical conductivity |
Test Results
TT502***
Unleaded Gasoline | |||
---|---|---|---|
1/3 MER* 334 m |
2/3 MER 665 m |
MER 995 m |
|
Response time (min) | 22.11 | 17.13 | 19.42 |
Product activation height (cm) | 1.53 | 1.53 | 1.53 |
Detection length (cm) | 61 | 61 | 61 |
Lower detection limits (cm) | |||
Product activation height | N/D* | N/D | 0.77 |
Detection length | N/D | N/D | 10 |
TT5000***
Unleaded Gasoline | |||
---|---|---|---|
1/3 MER 508 m |
2/3 MER 1016 m |
MER 1524 m |
|
Response time (min) | 12.02 | 9.18 | 7.51 |
Product activation height (cm) | 0.74 | 0.74 | 0.74 |
Detection length (cm) | 30.5 | 30.5 | 30.5 |
Lower detection limits (cm) | |||
Product activation height | N/D | N/D | 0.74 |
Detection length | N/D | N/D | 10 |
TT3000
3% by weight salt in water | Other solutions** | |||
---|---|---|---|---|
1/3 MER 508 m |
2/3 MER 1016 m |
MER 1524 m |
MER 1524 m |
|
Response time (min) | <1 | <1 | <1 | <1 |
Recovery time (min) | <1 | <1 | <1 | <1 |
Product activation height (cm) | <0.3 | <0.3 | <0.3 | <0.3 |
Detection length (cm) | <15.2 | <15.2 | <15.2 | <15.2 |
Lower detection limits (cm) | ||||
Product activation height | N/D | N/D | <0.3 | N/D |
Detection length | N/D | N/D | <5.08 | N/D |
**5% by volume oil in 3% by weight salt water, 10% by volume oil in 3% by weight salt water, 0.1 M hydrochloric acid (HCl), 0.1M sodium hydroxide (NaOH).
Specificity Results (in addition to above for TT502 and TT5000)
Activated: synthetic gasoline, diesel, heating oil #2, jet-A fuel (TT5000 only).
Not Activated: water.
Specificity Results (in addition to above for TT3000):
Activated: water
Not Activated: unleaded gasoline, synthetic gasoline, diesel, JP-8 fuel.
Comments
Evaluation also covered quantitative leak location.
TT502, TT5000 Fuel Sensing cable is not reusable.
Lower detection limit is calculated at MER only, and cable is assumed to be equally or more sensitive at shorter lengths.
***California regulations require sensors to be tested annually to verify proper operation. The detector is not reusable and must be replaced after contact with hydrocarbons.
- Tyco Thermal Controls LLC
300 Constitution Dr.
Menlo Park, CA 94025-1164
Tel: (800) 545-6258 - Evaluator: Carnegie Mellon Research Institute
Tel:(412) 268-3495
Date of Evaluation: 05/15/92, 12/20/95, 02/20/98
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.