Issue Date: November 22, 1995
Revision Date: April 17, 2003

Tyco Thermal Controls LLC

(originally listed as Raychem Corp.)

TraceTek Alarm and Locator Modules with TT502, TT5000, TT3000 Fuel Sensing Cable

Interstitial Detector (Liquid-Phase) and Liquid-Phase Out-Of-Tank Product Detector

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Electrical conductivity

Test Results

TT502***

  Unleaded Gasoline
  1/3 MER*
334 m
2/3 MER
665 m
MER
995 m
Response time (min) 22.11 17.13 19.42
Product activation height (cm) 1.53 1.53 1.53
Detection length (cm) 61 61 61
Lower detection limits (cm)
Product activation height N/D* N/D 0.77
Detection length N/D N/D 10

TT5000***

  Unleaded Gasoline
  1/3 MER
508 m
2/3 MER
1016 m
MER
1524 m
Response time (min) 12.02 9.18 7.51
Product activation height (cm) 0.74 0.74 0.74
Detection length (cm) 30.5 30.5 30.5
Lower detection limits (cm)
Product activation height N/D N/D 0.74
Detection length N/D N/D 10

TT3000

  3% by weight salt in water Other solutions**
  1/3 MER
508 m
2/3 MER
1016 m
MER
1524 m
MER
1524 m
Response time (min) <1 <1 <1 <1
Recovery time (min) <1 <1 <1 <1
Product activation height (cm) <0.3 <0.3 <0.3 <0.3
Detection length (cm) <15.2 <15.2 <15.2 <15.2
Lower detection limits (cm)
Product activation height N/D N/D <0.3 N/D
Detection length N/D N/D <5.08 N/D

*See glossary.

**5% by volume oil in 3% by weight salt water, 10% by volume oil in 3% by weight salt water, 0.1 M hydrochloric acid (HCl), 0.1M sodium hydroxide (NaOH).

Specificity Results (in addition to above for TT502 and TT5000)

Activated: synthetic gasoline, diesel, heating oil #2, jet-A fuel (TT5000 only).
Not Activated: water.

Specificity Results (in addition to above for TT3000):

Activated: water
Not Activated: unleaded gasoline, synthetic gasoline, diesel, JP-8 fuel.

Comments

Evaluation also covered quantitative leak location.
TT502, TT5000 Fuel Sensing cable is not reusable.
Lower detection limit is calculated at MER only, and cable is assumed to be equally or more sensitive at shorter lengths.
***California regulations require sensors to be tested annually to verify proper operation. The detector is not reusable and must be replaced after contact with hydrocarbons.

  • Tyco Thermal Controls LLC
    300 Constitution Dr.
    Menlo Park, CA 94025-1164
    Tel: (800) 545-6258
  • Evaluator: Carnegie Mellon Research Institute
    Tel:(412) 268-3495
    Date of Evaluation: 05/15/92, 12/20/95, 02/20/98

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.