Issue
Date: April 18, 1997
Revision Date: August 23, 1999
Universal
Sensors and Devices, Inc.
LTC-1000
(Mass Buoyancy Probe)
BULK
UNDERGROUND STORAGE TANK LEAK DETECTION METHOD (50,000 gallons
or greater)
Certification
|
Leak
rate is proportional to product surface area (PSA).
For tanks with PSA of 14,244 ft², leak rate is 1.4 gph
with PD = 97.2% and PFA = 2.8%.
For other tank sizes, leak rate equals [(PSA in ft² ÷
14,244 ft²) x 1.4 gph].
Example:
For a tank with PSA = 20,000 ft²; leak rate = [(20,000
ft² ÷ 14,244 ft²) x 1.4 gph] = 2.0 gph.
Calculated minimum detectable leak rate is 1.18 gph with
PD = 95% and PFA = 5%.
Leak rate may not be scaled below 0.2 gph.
|
Leak
Threshold
|
Leak
threshold is proportional to product surface area (PSA).
For tanks with PSA of 14,244 ft², leak threshold is 0.7
gph.
For other tank sizes, leak threshold equals [(PSA in ft²
÷ 14,244 ft²) x 0.7 gph].
Example:
For a tank with PSA = 20,000 ft²; leak threshold = [(20,000
ft² ÷ 14,244 ft²) x 0.7 gph] = 1.0 gph.
A tank system should not be declared tight if the test
result indicates a loss or gain that equals or exceeds
the calculated leak threshold.
|
Applicability
|
Gasoline,
diesel, aviation fuel, fuel oil #4.
Other liquids may be tested after consultation with the
manufacturer.
|
Tank
Capacity
|
Use
limited to single field-constructed vertical tanks larger
than 50,000 gallons.
Maximum product surface area (PSA) is 35,610 ft² (approximately
213 ft. diameter).
Performance not sensitive to product level.
|
Waiting
Time
|
Minimum
of 3 hours, 42 minutes after delivery.
Valve leaks and pump drain-back may mask a leak.
Allow sufficient waiting time to minimize these effects.
None between dispensing and testing.
|
Test
Period
|
Minimum
of 49 hours.
There must be no dispensing or delivery during test.
|
Temperature
|
Measurement
not required by this system.
|
Water
Sensor
|
None.
Water leaks are measured as increase in mass inside tank.
|
Calibration
|
Probe
must be checked and, if necessary, calibrated in accordance
with manufacturer's instructions.
|
Comments
|
Tests
only portion of tank containing product.
As product level is lowered, leak rate in a leaking tank
decreases (due to lower head pressure).
Consistent testing at low levels could allow a leak to
remain undetected.
Evaluated in a nominal 2,000,000 gallon, vertical underground
tank with product surface area (PSA) of 14,244 ft².
|
Universal
Sensors and Devices, Inc.
|
Evaluator: Ken Wilcox Associates
|
9205
Alabama Ave.
|
Tel: (816) 443-2494
|
Chatsworth,
CA
91311
|
Date
of Evaluation:
05/17/96
|
Tel: (800) 899-7121, (818) 988-7121
|
|
|