Issue Date: November 22, 1995
Revision Date: August 23, 1999
Universal Sensors and Devices, Inc.
Leak Alert System Models LAL-100, LA-01, LA-02, LA-04, LA-X4, LA-08, DLS-01, LS-20, LS-36, LS-70, CATLAS with LALS-1Liquid Sensor
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Thermal conductivity |
Test Results
Unleaded Gasoline | |
---|---|
Response time (min) | 1.24 |
Recovery time (min) | <1 |
Product activation height (cm) | 0.61 |
Lower detection limit (cm) | 0.76 |
Specificity Results (in addition to above):
Activated: synthetic gasoline, diesel, heating oil #2, water.
Comments
Sensors are reusable.
- Universal Sensors and Devices, Inc.
9205 Alabama Ave., Unit C
Chatsworth, CA 91311
Tel: (800) 899-7121, (818) 998-7121 - Evaluator: Carnegie Mellon Research Institute
Tel: (412) 268-3495
Date of Evaluation: 06/01/94, 04/22/97
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.