Issue Date: November 22, 1995
Revision Date: November 14, 1997

Vaporless Manufacturing

Vaporless LD-2000, LD-2000S

Automatic Mechanical Line Leak Detector

Certification Leak rate of 3.0 gph with PD = 100% and PFA = 0%.
Leak Threshold 1.7 gph.
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel.
Other liquids may be tested after consultation with the manufacturer.
Specification System tests pressurized fiberglass or steel pipelines.
Tests are conducted at operating pressure.
Pipeline Capacity Maximum of 129 gallons.
Waiting Time None between dispensing and testing.
None between delivery and testing.
Test Period Response time is 5 seconds.
System Features Permanent installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
LD2000 - restricted flow to dispenser if leak is declared.
LD2000S - pump shutoff if leak is declared.
Calibration Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions.
  • Vaporless Manufacturing
    8700 East Long Mesa Drive
    Prescott Valley, AZ 86314
    Tel: (520) 775-0185
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Dates of Evaluation: 11/19/90

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.