Issue Date: November 22, 1995
Revision Date: November 28, 2012
Vaporless Manufacturing
Vaporless 99 LD-3000, LD-3000, 99 LD-3000S, LD-3000S (for Rigid, Flexible, or Hybrid Combination of Rigid and Flexible Pipelines)
Automatic Mechanical Line Leak Detector
Certification | Leak rate of 3.0 gph with PD = 100% and PFA = 0%. |
---|---|
Leak Threshold | 2.0 gph. A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold. |
Applicability | Gasoline, diesel, aviation fuel. Other liquids may be tested after consultation with the manufacturer. |
Specification | System tests pressurized steel and fiberglass pipelines and combination of rigid and flexible pipelines. Tests are conducted at operating pressure. |
Pipeline Capacity | Maximum of 404 gallons for steel and fiberglass pipelines Maximum of 96 gallons for flexible pipelines Maximum combined capacity is 500 gallons, not to exceed the above individualcapacity limitations for combination rigid or flexible pipelines. |
Waiting Time | None between dispensing and testing. |
Test Period | Response time is 9 seconds. |
System Features | Permanent installation on pipeline. Automatic testing of pipeline. LD3000 - restricted flow to dispenser if leak is declared. LD3000S - pump shutoff if leak is declared. |
Calibration | Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions. |
Comments | Functionality and operability of the 99 LD-3000 are unchanged by installation of the Leak Detection Sensor (piston switch) that supports the VMI ISM-4080 and ISM-4081 Integrated Shutdown Module. |
- Vaporless Manufacturing
8700 East Long Mesa Drive
Prescott Valley, AZ 86314
Tel: (928) 775-5191 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Dates of Evaluation: 08/20/93 , 04/17/06
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.