Issue Date: November 22, 1995
Revision Date: August 8, 2017

Veeder-Root

ILS-350, TLS-350 Series, TLS-450 Series, TLS-4 8601 Series, Red Jacket ProMax with Adsistor Vapor Probe 794390-700

Out-Of-Tank Product Detector (Vapor-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Adsistor

Test Results

  Unleaded Gasoline Synthetic Gasoline JP-4 Jet Fuel
Detection time (min:sec) 7:46 N/A* 17:01
Fall time (min:sec) 2:38 N/A 3:05
Lower detection limit (ppm) 500 >1000 500

*See glossary.

Specificity Results (in addition to above)

Not Activated: n-hexane, toluene, xylene(s).
Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.

Calibration

Sensor must be checked annually for operability or in accordance with manufacturer's instructions and, if necessary, calibrated or replaced.

Comments

The TLS-4 8601 Series consists of the following derivatives: TLS-4, TLS-4B, TLS-4c, TLS-4i, and TLS-S1 consoles.

  • Veeder-Root
    125 Powder Forest Dr.
    Simsbury, CT 06070-2003
    Tel: (860) 651-2700
    URL: www.veeder.com/us/
  • Evaluator: Carnegie Mellon Research Institute
    Tel: (412) 268-3495
    Dates of Evaluation: 07/24/92

  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 3/3/2008, 1/11/17

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.