Issue Date: February 6, 2006 Revision Date: September 20, 2011
Veeder-Root
Red Jacket
FX1V, FX2V in Big Flow or Packer Manifold
(for Rigid and Flexible Pipelines)
AUTOMATIC MECHANICAL LINE
LEAK DETECTOR
Certification
|
Leak
rate of 3.0 gph with PD = 100% and PFA = 0%..
|
Leak
Threshold
|
1.5
gph at 10 psi. A pipeline system should not be declared tight if the
test result indicates a loss that equals or exceeds this threshold.
|
Applicability
|
Gasoline, ethanol blends up through E100.
|
Specification
|
System
tests pressurized pipelines. Tests are conducted at 8-12 psi.
|
Pipeline
Capacity
|
Maximum
of 416.7 gallons for rigid pipelines.
Maximum of 95.4 gallons for flexible pipelines.
|
Waiting
Time
|
None
between delivery and testing.
None between dispensing and testing.
Stabilization time up to 45 minutes may be required after dispensing
when temperature extremes are present.
|
Test
Period
|
Response time is
less than 5 minutes.
|
System
Features
|
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold. Total vertical rise of pipeline must not exceed 11 feet above leak detector.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared.
|
Calibration
|
Equipment
must be checked annually for capability of detecting a line leak of
3.0 gph and, if necessary, calibrated in accordance with manufacturer's
instructions.
|