Welcome to the State Water Resources Control Board Welcome to the California Environmental Protection Agency
Governor's Website Visit the Water Board Members Page
Agendas
My Water Quality
Performance Report
UST Program - LG 113

UST Programs - LG 113

Issue Date: November 22, 1995
Revision Date: November 21, 2003
 

Veeder-Root
(originally listed as Entropy Limited)

Precision Tank Inventory Control System, Revision 90

STATISTICAL INVENTORY RECONCILIATION TEST METHOD (QUANTITATIVE)

Certification Leak rate of 0.1 gph with PD = 99.5% and PFA < 0.5%.
"If a method meets the requirement for detecting a leak rate of 0.1 gph, it will meet the requirement for 0.2 gph.", according to "Standard Test Procedures for Evaluating Leak Detection Methods:
Statistical Inventory Reconciliation Methods", EPA/530/UST-90/007, June 1990, Section 7.2.3, page 30.
Leak Threshold If the absolute value of the calculated leak rate (gain or loss) is less than the leak threshold and the minimum detectable leak rate is less than or equal to 0.1 gph (0.2 gph for the 0.2 gph test), the test result is "pass." If the absolute value of the calculated leak rate is greater than or equal to the leak threshold, the result is "fail." If the minimum detectable leak rate exceeds 0.1 gph (0.2 gph for the 0.2 gph test) and the absolute value of the calculated leak rate is less than the leak threshold, the test result is "inconclusive."
Applicability Gasoline, diesel.
Other more viscous liquids may be tested after consultation with the vendor.
Tank Capacity Maximum of 22,500 gallons for single tanks.
Maximum of 60,000 gallons cumulative capacity for manifolded tank systems with no more than 3 tanks in system.
Data Requirement Minimum of 30 days of product level and flow through data.
Comments 32% of data sets evaluated were from manifolded tank systems.
Of 56 data sets submitted for evaluation, 6 were not analyzed due to unusable data and none were inconclusive.
Median monthly throughput of tanks evaluated was 52,207 gallons.
Leak rates ranging from 0.0497 to 0.203 gph were used in evaluation.
Data sets evaluated were supplied by evaluator.

 

Gilbarco/Veeder Root

Evaluator: Simpson, Gumpertz and Heger, Inc.

Attn: CMS Mailstop F-76

Tel:  (617) 643-2000

7300 West Friendly Ave.

Date of Evaluation:  11/30/93

P.O. Box 22087  
Greensboro, NC 27420-2087  

Tel:  (800) 253-8054

 