Issue Date: November 22, 1995
Revision Date: June 24, 2002
Veeder-Root
(originally listed as Gilbarco Environmental Products and later as Marconi Commerce Systems)
EMC Environmental Management Console EMC Basic Monitoring System Tank Monitors 2, 3, 2.1, 3.1, PAO238000XXXX (Same as Veeder-Root Model 7842) (Capacitance Probe)
Automatic Tank Gauging Method
Certification | Leak rate of 0.2 gph with PD = 99% and PFA = 1%. |
---|---|
Leak Threshold | 0.1 gph. A tank system should not be declared tight if the test result indicates a loss or gain that equals or exceeds this threshold. |
Applicability | Gasoline, diesel, aviation fuel. Other liquids with known coefficients of expansion and density may be tested after consultation with the manufacturer. |
Tank Capacity | Maximum of 15,000 gallons. Tank must be between 50 and 95% full. |
Waiting Time | Minimum of 8 hours, 18 minutes between delivery and testing. There must be no dispensing or delivery during waiting time. |
Test Period | Minimum of 5 hours. Test data are acquired and recorded by system's computer. Leak rate is calculated from the difference between the first and last data collected. There must be no dispensing or delivery during test. |
Temperature | Average for product is obtained by a temperature averaging probe. |
Water Sensor | Must be used to detect water ingress. Minimum detectable water level in the tank is 1.40 inches. Minimum detectable change in water level is 0.040 inch. |
Calibration | Temperature averaging probe must be checked and, if necessary, calibrated in accordance with manufacturer's instructions. |
Comments | Not evaluated using manifolded tank systems. California regulations require at least one test per month after routine product delivery or when the tank is filled to within 10% of the highest operating level of previous month. |
- Veeder-Root
125 Powder Forest Dr.
Simsbury, CT 06070-2003
Tel: (860) 651-2700 - Evaluator: Midwest Research Institute
Tel: (816) 753-7600
Date of Evaluation: 05/14/93
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.