Issue Date: November 22, 1995
Revision Date: June 24, 2002

Veeder-Root

(originally listed as Gilbarco Environmental Products and later as Marconi Commerce Systems)

PA02590XXX000, (Same as Veeder-Root 794390-409), PA02591144000, (Same as Veeder-Root 794390-420), PA02592000010, (Same as Veeder-Root 794380-208)

Interstitial Detector (Liquid-Phase)

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Float switch

Test Results

PA02590XXX000

  Unleaded Gasoline Synthetic Gasoline
Response time (min) 3.66 3.45
Recovery time (min) <1 <1
Product activation height (cm) 1.28 1.27
Lower detection limit (cm) 1.84 1.65

PA02591144000

  Unleaded Gasoline Synthetic Gasoline
Response time (min) 6.00 6.51
Recovery time (min) <1 <1
Product activation height (cm) 3.67 3.62
Lower detection limit (cm) 4.05 4.17

PA02592000010

  Unleaded Gasoline Synthetic Gasoline
Response time (min) 8.19 8.49
Recovery time (min) <1 <1
Product activation height (cm) 4.12 3.95
Lower detection limit (cm) 4.67 4.36

Specificity Results (in addition to above)

Activated: diesel, heating oil #2, water.

Comments

Sensors are reusable.

  • Veeder-Root
    125 Powder Forest Dr.
    Simsbury, CT 06070-2003
    Tel: (860) 651-2700
  • Evaluator: Carnegie Mellon Research Institute
    Tel: (412) 268-3495
    Date of Evaluation: 07/17/92, 04/22/98

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.