Issue Date: October 19, 2007
Revision Date: June 27, 2011

Western Fiberglass, Inc.

Liquid-Filled Reservoir for Double-Wall Sumps with Liquid Sensor Models WF-3 and WF-750

Continuous Interstitial Monitoring Method (Liquid Filled)

Certification Certified as a continuous, liquid-filled interstitial space leak detection system for use only with Western Fiberglass, Inc., double-walled sumps or under dispenser containment sumps.
Operating Principle Hydrostatic monitoring using single-level float switch. Methodology is similar to that which has been applied to liquid-filled interstitial double-walled tanks.
Propylene glycol is used to fill the interstice of Western Fiberglass' double-walled sumps or under dispenser containment sumps.
An interstitial liquid reservoir is connected to a port at the highest point of the double-walled space.
Single-level liquid sensor model WF-3 or WF-750 monitor the liquid in the interstitial reservoir and provide an alarm if the liquid drops too low (egress of liquid).
Alarm Conditions
  0.05 gph Leak, Plastic Reservoir with WF-3 Sensor 0.05 gph Leak, Stainless Steel Reservoir with WF-750 Sensor
Normal Liquid Volume Minimum Liquid Volume Normal Liquid Volume Minimum Liquid Volume
*Volume of Liquid Lost at Alarm (ml) 41.8 2.5 74.3 16.7
Time to Alarm (min) <1 <1 <1 <1
Time to Reset (min) <1 <1 <1 <1

*Volume of liquid lost to alarm depends on the amount of liquid in the reservoir. This amount is determined by the operator when filling the reservoir. This amount needs to be sufficient to prevent false alarms from occurring due to the normal fluctuations in the reservoir which result from temperature and pressure variations in the sump. Minimum alarm volumes were obtained by filling the reservoir to the lowest possible level to reset the alarm. While this condition provides the shortest response time, it is also subject to the highest false alarm rate.

Applicability Western Fiberglass, Inc. underground double-walled sumps and under dispenser sumps designed to contain water, gasoline, gasohol, diesel, heating oil #2, kerosene, aviation fuel, or motor oil. Other liquids may be stored after consultation with the manufacturer.
Calibration Reservoir requires no calibration other than to insure the upper reservoir is half full.
Sensors must be calibrated and maintained in accordance with manufacturer's instructions.
Comments Fluid reservoir volumes and connection tightness between reservoir and sump should be inspected annually.
Liquid level in the stainless steel reservoir should be visible in the sight glass.
Liquid level in the plastic reservoir should be approximately one inch above the float switch.
  • Western Fiberglass, Inc.
    1555 Copperhill Parkway
    Santa Rosa, CA 95403
    Tel: (707) 523-2050
    Email: sales@westernfg.com
    URL: www.westernfg.com
  • Evaluator: Ken Wilcox Associates
    Tel: (816) 443-2494
    Date of Evaluation: 12/20/2006

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.